◆ High frequency on-line double conversion
◆ Output power factor 1.0
◆ DSP (Digital signal processors) control
◆ Active input power factor correction, input power factor>0.99
◆ Three level inverter technology, lower harmonic, higher efficiency
◆ Wide input voltage range 90V~300V and frequency range 40~70Hz
◆ Generator compatible
◆ Cold start function
◆ Remote on off (ROO) function (optional)
◆ Economic operation mode (ECO)
◆ 50Hz/60Hz Frequency auto sensing
◆ Frequency converter mode: 50Hz input / 60Hz output or 60Hz input / 50Hz output
◆ Laser printer and ultrasound system load acceptable (customized)
◆ Support CVCF (Constant Voltage,Constant Frequency) mode, support special voltage,frequency devices, and suitable for highly sensitive devices
◆ Communications:RS232(standard), USB / MODBUS / RS485 / SNMP / AS400 card (optional)
◆ Reliable design, made with strong glass fiber base (FR4) double side PCB, well designed ventilation and conformal coating
We were established in 2015 , have two producing bases , 5 production line and monthly produce about 80,000 pieces.
Our ODM & OEM production is strictly based on the IS09001 and service customers in need.
REO is a one top power solution provider and warmly welcome to be our distributor and partner
Accept Deeply Customized Products
Model | Maxwin 31 10K | Maxwin 31 10KL | Maxwin 31 15K | Maxwin 31 15KL | Maxwin 31 20K | Maxwin 31 20KL |
Capacity | 10KVA/10KW | 15KVA/15KW | 20KVA/20KW | |||
Phase | Single phase input single phase output or 3 phases input single phase output | |||||
AC INPUT | ||||||
Wiring | Single Phase L/N+PE or 3 Phases (L1,L2,L3)/N+PE | |||||
Rated Voltage | 208/220/230/240VAC | |||||
Voltage Range | Line-Neutral 90~300VAC ; Line-Line 150~500VAC | |||||
Frequency Range | 40Hz-70Hz | |||||
Input Power Factor | ≥0.99 | |||||
AC OUTPUT | ||||||
Wiring | L/N+PE | |||||
Rated Output Voltage | 208/220/230/240VAC | |||||
Voltage Regulation | ±1% | |||||
Output Frequency | 50/60±4Hz (Synchronized range); 50/60Hz±0.1(Battery mode) | |||||
Waveform | Pure sine wave | |||||
Power Factor | 1.0 | |||||
Distortion (THDV%) | <2% (Linear Load) ; <7% (Non-Linear Load) | |||||
Overload Capability | 10Min@105%~125% rated load 60Sec.@125%~150% rated load 0.5Sec.@>150% rated load |
|||||
EFFICIENCY | ||||||
Line Mode | 94% @240VDC, 92% @192VDC | |||||
Battery Mode | 94% @240VDC, 92% @192VDC | |||||
ECO mode | 97% | |||||
BATTERY & CHARGER | ||||||
Rated Battery Voltage | 192VDC | 192/240VDC External Battery |
192VDC | 192/240VDC External Battery |
192VDC | 192/240VDC External Battery |
Battery Capacity | 12V/7AH x16pcs | External Battery Depends | 12V/7AH x 32pcs | External Battery Depends | 12V/9AH x 32pcs | External Battery Depends |
Backup Time | >10mins @half load | >10mins @half load | >10mins @half load | |||
Charging Current | Standard model with internal battery, 10K: 2A/4A (settable by LCD) ; 15K~20K: 4A Long backup time model: 4A/8A (optional) |
|||||
Optional Configuration to Order | 1. Battery capacity 7AH/9AH 2. Battery quantity 16pcs or 32pcs |
|||||
HMI | ||||||
LCD Display | Input mains voltage, frequency, load level, operation mode, health status | |||||
Standards Communication Interface | (1) RS232 port | |||||
Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP card |
|||||
ENVIRONMENT | ||||||
Temperature Range | -10~50oC | |||||
Relative Humidity | 0-98%(Non-condensing) | |||||
Acoustics Noise | <60dB @ 1 meters | |||||
PHYSICAL | ||||||
Dimension WxDxH (mm) |
190x662x482 | 190x574x340 | 300x698x700 | 239x581x529 | 300x698x700 | 239x581x529 |
N.W (kg) | 52.9 | 14.6 | 88.7 | 25.9 | 88.9 | 26.4 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model