◆ High frequency on-line double conversion
◆ Output power factor 1.0
◆ DSP (Digital signal processors) control
◆ Active input power factor correction, input power factor>0.99
◆ 6-20K three level inverter technology, lower harmonic, higher efficiency
◆ Wide input voltage range 90V~300V and frequency range 40~70Hz
◆ Generator compatible
◆ Cold start function
◆ Remote on off (ROO) function (optional)
◆ Economic operation mode (ECO)
◆ 50Hz/60Hz Frequency auto sensing
◆ Frequency converter mode: 50Hz input / 60Hz output or 60Hz input / 50Hz output
◆ Laser printer and ultrasound system load acceptable (customized)
◆ Support CVCF (Constant Voltage,Constant Frequency) mode, support special voltage,frequency devices, and suitable for highly sensitive devices
◆ Communications:RS232(standard), USB / MODBUS / RS485 / SNMP / AS400 card (optional)
◆ Reliable design, made with strong glass fiber base (FR4) double side PCB, well designed ventilation and conformal coating
We were established in 2015 , have two producing bases , 5 production line and monthly produce about 80,000 pieces.
Our ODM & OEM production is strictly based on the IS09001 and service customers in need.
REO is a one top power solution provider and warmly welcome to be our distributor and partner
Accept Deeply Customized Products
| Model | Maxwin 1KR | Maxwin 1KRL | Maxwin 2KR | Maxwin 2KRL | Maxwin 3KR | Maxwin 3KRL |
| Capacity | 1KVA/1KW | 2KVA/2KW | 3KVA/3KW | |||
| AC INPUT | ||||||
| Wiring | L/N+PE | |||||
| Rated Voltage | 208/220/230/240VAC | |||||
| Voltage Range | 90~300VAC | |||||
| Frequency Range | 40Hz~70Hz | |||||
| Input Power Factor | ≥0.99 | |||||
| AC OUTPUT | ||||||
| Wiring | L/N+PE | |||||
| Output Voltage | 208/220/230/240VAC | |||||
| Voltage Regulation | ±1% | |||||
| Output Frequency | 50/60±4Hz(Synchronized range); 50/60Hz±0.1(Battery mode) | |||||
| Waveform | Pure sine wave | |||||
| Power Factor | 1.0 | |||||
| Distortion(THDV%) | <2%(Linear Load); <7%(Non-Linear Load) | |||||
| Over load capability | 1Min@105%~125% rated load ; 30Sec.@125%~150% rated load; 0.5Sec.@>150% rated load | |||||
| EFFICIENCY | ||||||
| Line Mode | 89% | 90% | 91% | |||
| Battery Mode | 86% | 87% | 88% | |||
| ECO mode | 95% | |||||
| BATTERY & CHARGER | ||||||
| Rated Battery Voltage | 24VDC Internal |
36VDC External |
48VDC Internal |
72VDC External |
72VDC Internal |
72VDC External |
| Battery Capacity | 12V/7AH x2pcs | External Battery Depends | 12V/7AHx4pcs | External Battery Depends | 12V/7AHx6pcs | External Battery Depends |
| Backup Time | >6mins @ Half Load | >6mins @ Half Load | >6mins @ Half Load | |||
| Charging Current | Standard model with internal battery:1A ; Long bbackup time model :4A | |||||
| Optional Configuration to Order | 1. External battery socket for standard model 2. Battery capacity 7AH/9AH 3. Battery quantity(2/4/6pcs) or (3/6/6pcs) |
|||||
| HMI | ||||||
| LCD DISPLAY | Input mains voltage, frequency, load level, operation mode, health status | |||||
| Standards Communication Interface | (1) RS232 port | |||||
| Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP card |
|||||
| ENVIRONMENT | ||||||
| Temperature Range | -10~50oC | |||||
| Relative Humidity | 0-98%(Non-condensing) | |||||
| Acoustics Noise | <55dB @ 1 meters | |||||
| PHYSICAL | ||||||
| Dimension WxDxH (mm) |
440x400x88 (2U) | 440x400x88 (2U) | 440x400x88 (2U) | 440x400x88 (2U) | 440x612x88 (2U) | 440x400x88 (2U) |
| N.W (kg) | 11.4 | 6.7 | 16 | 7.3 | 23.2 | 8.9 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model
Accept Deeply Customized Products
| Model | Maxwin 6KRL | Maxwin 10KRL |
| Capacity | 6KVA/6KW | 10KVA/10KW |
| AC INPUT | ||
| Wiring | L/N+PE | |
| Rated Voltage | 208/220/230/240Vac | |
| Voltage Range | 90~300VAC | |
| Frequency Range | 40Hz-70Hz | |
| Input Power Factor | ≥0.99 | |
| AC OUTPUT | ||
| Wiring | L/N+PE | |
| Output Voltage | 208/220/230/240VAC | |
| Voltage Regulation | ±1% | |
| Output Frequency | 50/60±4Hz (Synchronized range); 50/60Hz±0.1(Battery mode) | |
| Waveform | Pure Sine Wave | |
| Power Factor | 1.0 | |
| Distortion (THDV%) | <2%(Linear Load) ; <7%(None-Linear Load) | |
| Overload Capability | 10Min@105%~125% rated load 60Sec.@125%~150% rated load 0.5Sec.@>150% rated load |
|
| EFFICIENCY | ||
| Line Mode | 94% @240VDC, 92% @192VDC | |
| Battery Mode | 94% @240VDC, 92% @192VDC | |
| ECO mode | 97% | |
| BATTERY & CHARGER | ||
| Rated Battery Voltage | 192/240VDC External Battery | |
| Battery Capacity | Depend on the capacity of external battery | |
| Backup Time | Depend on the capacity of external battery | |
| Charging Current | Long backup time model :4A | |
| HMI | ||
| LCD Display | Input mains voltage, frequency, load level, operation mode, health status | |
| Standards Communication Interface | (1) RS232 port | |
| Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP card |
|
| ENVIRONMENT | ||
| Temperature range | -10~50oC | |
| Relative Humidity | 0-98%(Non-condensing) | |
| Acoustics Noise | <55dB @ 1 meters | |
| PHYSICAL | ||
| Dimension WxDxH (mm) |
440x493x88(2U) | |
| N.W (kg) | 10.8 | 12.6 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model
Accept Deeply Customized Products
| Model | Maxwin 31 10KRL | Maxwin 31 15KRL | Maxwin 31 20KRL |
| Capacity | 10KVA/10KW | 15KVA/15KW | 20KVA/20KW |
| Phase | 1 phase in/1 phase out or 3 phase in/1 phase out | ||
| AC INPUT | |||
| Wiring | Single phase (L/N+PE) or 3 phases (L1,L2,L3)/N+PE | ||
| Rated Voltage | 208/220/230/240VAC | ||
| Voltage Range | Line-Neutral 90~300VAC ; Line-Line 150~500VAC | ||
| Frequency Range | 40Hz~70Hz | ||
| Input Power Factor | ≥0.99 | ||
| AC OUTPUT | |||
| Wiring | L/N+PE | ||
| Rated Output Voltage | 208/220/230/240VAC | ||
| Voltage Regulation | ±1% | ||
| Output Frequency | 50/60±4Hz(Synchronized range); 50/60Hz±0.1(Battery mode) | ||
| Waveform | Pure sine wave | ||
| Power Factor | 1.0 | ||
| Distortion (THDV%) | <2%(Linear Load) ; <7%(Non-Linear Load) | ||
| Overload capability | 10Min@105%~125% rated load, 60Sec.@125%~150% rated load, 0.5Sec.@>150% rated load. | ||
| EFFICIENCY | |||
| Line Mode | 94% @240VDC, 92% @192VDC | ||
| Battery Mode | 94% @240VDC, 92% @192VDC | ||
| ECO mode | 97% | ||
| BATTERY & CHARGER | |||
| Rated Battery Voltage | 192/240VDC external battery | ||
| Battery Capacity | Depend on the capacity of external battery | ||
| Backup Time | Depend on the capacity of external battery | ||
| Charging Current | Long backup time model : 4A / 8A (optional) | ||
| HMI | |||
| LCD Display | Input mains voltage, frequency, load level, operation mode, health status | ||
| Standards Communication Interface | (1) RS232 port | ||
| Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP cardrd |
||
| ENVIRONMENT | |||
| Temperature Range | -10~50oC | ||
| Relative Humidity | 0-98%(Non-condensing) | ||
| Acoustics Noise | <60dB @ 1 meters | ||
| PHYSICAL | |||
| Dimension WxDxH (mm) |
440x502x132 (3U) | 440x532x176 (4U) | |
| N.W(kg) | 14.4 | 24.1 | 24.1 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model