◆ High frequency on-line double conversion
◆ Output power factor 1.0
◆ DSP (Digital signal processors) control
◆ Active input power factor correction, input power factor>0.99
◆ 6-20K three level inverter technology, lower harmonic, higher efficiency
◆ Wide input voltage range 90V~300V and frequency range 40~70Hz
◆ Generator compatible
◆ Cold start function
◆ Remote on off (ROO) function (optional)
◆ Economic operation mode (ECO)
◆ 50Hz/60Hz Frequency auto sensing
◆ Frequency converter mode: 50Hz input / 60Hz output or 60Hz input / 50Hz output
◆ Laser printer and ultrasound system load acceptable (customized)
◆ Support CVCF (Constant Voltage,Constant Frequency) mode, support special voltage,frequency devices, and suitable for highly sensitive devices
◆ Communications:RS232(standard), USB / MODBUS / RS485 / SNMP / AS400 card (optional)
◆ Reliable design, made with strong glass fiber base (FR4) double side PCB, well designed ventilation and conformal coating
We were established in 2015 , have two producing bases , 5 production line and monthly produce about 80,000 pieces.
Our ODM & OEM production is strictly based on the IS09001 and service customers in need.
REO is a one top power solution provider and warmly welcome to be our distributor and partner
Accept Deeply Customized Products
Model | Maxwin 1KR | Maxwin 1KRL | Maxwin 2KR | Maxwin 2KRL | Maxwin 3KR | Maxwin 3KRL |
Capacity | 1KVA/1KW | 2KVA/2KW | 3KVA/3KW | |||
AC INPUT | ||||||
Wiring | L/N+PE | |||||
Rated Voltage | 208/220/230/240VAC | |||||
Voltage Range | 90~300VAC | |||||
Frequency Range | 40Hz~70Hz | |||||
Input Power Factor | ≥0.99 | |||||
AC OUTPUT | ||||||
Wiring | L/N+PE | |||||
Output Voltage | 208/220/230/240VAC | |||||
Voltage Regulation | ±1% | |||||
Output Frequency | 50/60±4Hz(Synchronized range); 50/60Hz±0.1(Battery mode) | |||||
Waveform | Pure sine wave | |||||
Power Factor | 1.0 | |||||
Distortion(THDV%) | <2%(Linear Load); <7%(Non-Linear Load) | |||||
Over load capability | 1Min@105%~125% rated load ; 30Sec.@125%~150% rated load; 0.5Sec.@>150% rated load | |||||
EFFICIENCY | ||||||
Line Mode | 89% | 90% | 91% | |||
Battery Mode | 86% | 87% | 88% | |||
ECO mode | 95% | |||||
BATTERY & CHARGER | ||||||
Rated Battery Voltage | 24VDC Internal |
36VDC External |
48VDC Internal |
72VDC External |
72VDC Internal |
72VDC External |
Battery Capacity | 12V/7AH x2pcs | External Battery Depends | 12V/7AHx4pcs | External Battery Depends | 12V/7AHx6pcs | External Battery Depends |
Backup Time | >6mins @ Half Load | >6mins @ Half Load | >6mins @ Half Load | |||
Charging Current | Standard model with internal battery:1A ; Long bbackup time model :4A | |||||
Optional Configuration to Order | 1. External battery socket for standard model 2. Battery capacity 7AH/9AH 3. Battery quantity(2/4/6pcs) or (3/6/6pcs) |
|||||
HMI | ||||||
LCD DISPLAY | Input mains voltage, frequency, load level, operation mode, health status | |||||
Standards Communication Interface | (1) RS232 port | |||||
Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP card |
|||||
ENVIRONMENT | ||||||
Temperature Range | -10~50oC | |||||
Relative Humidity | 0-98%(Non-condensing) | |||||
Acoustics Noise | <55dB @ 1 meters | |||||
PHYSICAL | ||||||
Dimension WxDxH (mm) |
440x400x88 (2U) | 440x400x88 (2U) | 440x400x88 (2U) | 440x400x88 (2U) | 440x612x88 (2U) | 440x400x88 (2U) |
N.W (kg) | 11.4 | 6.7 | 16 | 7.3 | 23.2 | 8.9 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model
Accept Deeply Customized Products
Model | Maxwin 6KRL | Maxwin 10KRL |
Capacity | 6KVA/6KW | 10KVA/10KW |
AC INPUT | ||
Wiring | L/N+PE | |
Rated Voltage | 208/220/230/240Vac | |
Voltage Range | 90~300VAC | |
Frequency Range | 40Hz-70Hz | |
Input Power Factor | ≥0.99 | |
AC OUTPUT | ||
Wiring | L/N+PE | |
Output Voltage | 208/220/230/240VAC | |
Voltage Regulation | ±1% | |
Output Frequency | 50/60±4Hz (Synchronized range); 50/60Hz±0.1(Battery mode) | |
Waveform | Pure Sine Wave | |
Power Factor | 1.0 | |
Distortion (THDV%) | <2%(Linear Load) ; <7%(None-Linear Load) | |
Overload Capability | 10Min@105%~125% rated load 60Sec.@125%~150% rated load 0.5Sec.@>150% rated load |
|
EFFICIENCY | ||
Line Mode | 94% @240VDC, 92% @192VDC | |
Battery Mode | 94% @240VDC, 92% @192VDC | |
ECO mode | 97% | |
BATTERY & CHARGER | ||
Rated Battery Voltage | 192/240VDC External Battery | |
Battery Capacity | Depend on the capacity of external battery | |
Backup Time | Depend on the capacity of external battery | |
Charging Current | Long backup time model :4A | |
HMI | ||
LCD Display | Input mains voltage, frequency, load level, operation mode, health status | |
Standards Communication Interface | (1) RS232 port | |
Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP card |
|
ENVIRONMENT | ||
Temperature range | -10~50oC | |
Relative Humidity | 0-98%(Non-condensing) | |
Acoustics Noise | <55dB @ 1 meters | |
PHYSICAL | ||
Dimension WxDxH (mm) |
440x493x88(2U) | |
N.W (kg) | 10.8 | 12.6 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model
Accept Deeply Customized Products
Model | Maxwin 31 10KRL | Maxwin 31 15KRL | Maxwin 31 20KRL |
Capacity | 10KVA/10KW | 15KVA/15KW | 20KVA/20KW |
Phase | 1 phase in/1 phase out or 3 phase in/1 phase out | ||
AC INPUT | |||
Wiring | Single phase (L/N+PE) or 3 phases (L1,L2,L3)/N+PE | ||
Rated Voltage | 208/220/230/240VAC | ||
Voltage Range | Line-Neutral 90~300VAC ; Line-Line 150~500VAC | ||
Frequency Range | 40Hz~70Hz | ||
Input Power Factor | ≥0.99 | ||
AC OUTPUT | |||
Wiring | L/N+PE | ||
Rated Output Voltage | 208/220/230/240VAC | ||
Voltage Regulation | ±1% | ||
Output Frequency | 50/60±4Hz(Synchronized range); 50/60Hz±0.1(Battery mode) | ||
Waveform | Pure sine wave | ||
Power Factor | 1.0 | ||
Distortion (THDV%) | <2%(Linear Load) ; <7%(Non-Linear Load) | ||
Overload capability | 10Min@105%~125% rated load, 60Sec.@125%~150% rated load, 0.5Sec.@>150% rated load. | ||
EFFICIENCY | |||
Line Mode | 94% @240VDC, 92% @192VDC | ||
Battery Mode | 94% @240VDC, 92% @192VDC | ||
ECO mode | 97% | ||
BATTERY & CHARGER | |||
Rated Battery Voltage | 192/240VDC external battery | ||
Battery Capacity | Depend on the capacity of external battery | ||
Backup Time | Depend on the capacity of external battery | ||
Charging Current | Long backup time model : 4A / 8A (optional) | ||
HMI | |||
LCD Display | Input mains voltage, frequency, load level, operation mode, health status | ||
Standards Communication Interface | (1) RS232 port | ||
Optional | (2) EPO / ROO port (3) Intelligent slot (4) USB port (5) NMC Card: Support remote monitor the UPS via Smart phone APP, web page,PC monitor software , support server / NAS shutdown (6) CMC MODBUS card (7) AS400 Relay card (8) SNMP cardrd |
||
ENVIRONMENT | |||
Temperature Range | -10~50oC | ||
Relative Humidity | 0-98%(Non-condensing) | ||
Acoustics Noise | <60dB @ 1 meters | ||
PHYSICAL | |||
Dimension WxDxH (mm) |
440x502x132 (3U) | 440x532x176 (4U) | |
N.W(kg) | 14.4 | 24.1 | 24.1 |
• Product specifications are subject to change without prior notice
• Ambient temperature>30°C, output power factor is 0.9
• Model with”L” mean long back up time model, without “L” mean standard model